Contactor maintenance

Regular maintenance and inspection of contactors are essential to ensure their reliable operation and extend their service life. Before performing any checks or repairs, always disconnect the power supply to avoid electrical hazards. Follow these steps carefully:

1. Visual Inspection

Start by cleaning the contactor with a soft cloth slightly dampened with gasoline to remove oil and dirt. Wipe it again with a dry cloth to ensure no residue remains. Check all terminal screws and tighten them if necessary to prevent loosening, which can lead to overheating at connection points.

2. Arc Suppression Cover Maintenance

1) Remove the arc suppression cover and use a brush to clean out any debris or metal particles inside. If the cover is cracked or damaged, replace it immediately.

2) For grid-type arc suppression covers, inspect the grid for signs of damage, burning, deformation, or looseness. If the damage is severe and cannot be repaired, replace the cover entirely.

3. Contact System Inspection

1) Ensure that the moving and stationary contacts are properly aligned and that all three phases close simultaneously. Adjust the contact spring as needed to maintain consistent contact pressure.

2) Measure the interphase insulation resistance using a 500V megohmmeter. The resistance should be at least 10 megohms.

3) If the contact thickness wears down more than 1 mm or if there is significant burning, replace the contact. Minor burns or surface discoloration that do not affect performance can be left as is. If the contact surface is uneven, gently smooth it with a small file.

4) After repairing or replacing contacts, check the contact gap and over-travel. Proper over-travel ensures adequate contact pressure during operation.

5) Test the auxiliary contacts for smooth operation. Check if the static contacts are loose or missing. Measure the contact resistance with a multimeter. If the contact is faulty and cannot be repaired, replace it with a new one.

4. Core Maintenance

1) Clean the core’s end face using cotton yarn and gasoline to remove oil or dust.

2) Check if the buffer components are intact and correctly positioned.

3) Inspect the rivets to ensure they are not broken, which could cause the core to become loose.

4) Look for any cracks or breaks in the short-circuit ring. If the ring is damaged or making unusual noise, replace it along with the core.

5) Verify that the electromagnet is in good condition and that there is no misalignment or poor contact.

5. Electromagnetic Coil Maintenance

1) The AC contactor’s coil should operate reliably when the voltage is between 85% and 105% of its rated voltage.

2) Check for overheating by examining the coil’s outer surface for discoloration or aging. Overheating may indicate a turn-to-turn short circuit. Measure the coil’s resistance and compare it with a similar one. If it cannot be repaired, replace the coil.

3) Ensure that the lead wires and terminals are securely connected and not burnt or disconnected.

4) Inspect the coil bobbin for cracks, wear, or improper mounting. If found, fix or replace it immediately to prevent further damage.